SUINT3000LCD2U

Còn hàng

Tổng quan

Overview The SUINT3000LCD2U SmartOnline® 3000VA/2700W On-Line Double-Conversion UPS converts AC input to DC power, and then converts DC to fully regulated sine wave AC output with +/-2% voltage regulation in online and battery modes. An interactive front-panel LCD interface provides detailed real-time UPS status and advanced setup and configuration options. In case of AC power outage, the internal batteries support 13.5 minutes of runtime at half load and five minutes at full load. Extended runtime is possible with optional external battery packs. “Smart” battery packs, such as Tripp Lite’s BP72V18-2US , are automatically sensed and configured during...

Overview

The SUINT3000LCD2U SmartOnline® 3000VA/2700W On-Line Double-Conversion UPS converts AC input to DC power, and then converts DC to fully regulated sine wave AC output with +/-2% voltage regulation in online and battery modes. An interactive front-panel LCD interface provides detailed real-time UPS status and advanced setup and configuration options.

In case of AC power outage, the internal batteries support 13.5 minutes of runtime at half load and five minutes at full load. Extended runtime is possible with optional external battery packs. “Smart” battery packs, such as Tripp Lite’sBP72V18-2US, are automatically sensed and configured during replacement. An intelligent battery management system extends battery life.

Managing the UPS is simplified through the interactive front-panel LCD interface, which displays operating conditions and diagnostic data, such as load and battery levels. You can set power strategies to reflect your protection priorities, whether it’s precise power quality for sensitive systems or the highest possible electrical efficiency, all while ensuring 100% uptime for your systems. This UPS is ENERGY STAR qualified to save you money, save energy and protect the environment by meeting strict efficiency guidelines set by the U.S. Environmental Protection Agency.

Power is filtered to protect connected equipment against surges and EMI/RFI line noise that can damage equipment or destroy data. Tested to international and North American CE, IEC62040-1: 2008, UL 1778, CSA, SASO and EAC standards for applications worldwide. Adding an optional Tripp Lite SNMPWEBCARD accessory card permits remote management of the UPS, including reboots and activity logs.

Features

Protects Mission-Critical Rack-Mounted Equipment

  • Converts AC input to DC power, then DC to fully regulated sine wave AC output
  • +/-2% voltage regulation in online and battery modes
  • Selectable 200/208/220/230/240V output voltage
  • 3000VA/2700W capacity
  • 2 C19 and 8 C13 outlets
  • 570-joule surge suppression rating


Interactive Front-Panel LCD

  • Reports detailed status information, including load and battery levels
  • Offers advanced configuration options, including output voltage and power strategies


5 Power Strategies

  • Auto Adaptive enables high efficiency and high-quality operation as necessary for ideal equipment protection
  • Max Efficiency favors economy operation with high 95% efficiency
  • Max Quality favors on-line, double-conversion mode, maintaining +/-2% output voltage regulation and zero transfer time
  • Frequency Regulation and Frequency Conversion enable +/-0.05 Hz output regulation for selected frequency(50/60 Hz)


Reliable, Expandable Battery Backup

  • Supports half load(1350W) for 13.5 min. and full load(2700W) for 5 min.
  • Add external battery packs for extra runtime
  • “Smart” battery packs, such as Tripp Lite’s BP72V18-2US, are automatically sensed and configured during replacement
  • Full 2700W capacity available with and without external battery packs
  • Battery independent restart ensures automatic UPS power-up after lengthy power outages, even with expired batteries


Highly Customizable

  • Customize communications and behavior to integrate with device makers’ specific needs
  • Selectable auto-restart from 0 to 60 sec. after AC power is restored
  • Selectable minimum battery charge level before auto-restart
  • Schedule system reboot if USB signal from connected device is lost
  • Set overload thresholds and low battery levels for alert and shutdown
  • Remote on/off(toggle) support via DB9


Certified for Efficiency and Worldwide Use

  • ENERGY STAR qualified to save you money, save energy and protect the environment by meeting strict EPA efficiency guidelines
  • Tested to international and North American CE, IEC62040-1: 2008, UL 1778, CSA, SASO and EAC standards for applications worldwide


SNMP/Web Capability

  • Optional Tripp Lite SNMPWEBCARD permits remote management of UPS, including reboots, configuration, updates and activity logs

  

Package Includes

  • SUINT3000LCD2U SmartOnline 3000VA/2700W On-Line Double-Conversion UPS
  • 4-post rack-mount installation kit
  • USB cable
  • RS-232 cable
  • C19-to-C20 power cable
  • (2) C13-to-C14 power cables
  • Owner’s manual
OUTPUT
Output Volt Amp Capacity (VA) 3000
Output kVA Capacity (kVA) 3
Output Watt Capacity (Watts) 2700
Output kW Capacity (kW) 2.7
Output Capacity Details DE-RATING INFORMATION: Max output in Frequency Conversion mode is reduced to 1890 watts for 208/220/230/240V output voltages; Max output is reduced to 2160W at 200V output voltage in all operating modes OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for 30 seconds and >150% for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits).
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s) Supported 200V; 208V; 220V; 230V; 240V
Nominal Voltage Details Nominal output voltage is user configured on first power-on
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details Output frequency matches input nominal on startup; Output capacity de-rates by 30% during frequency conversion operation
Output Voltage Regulation (Line Mode) +/- 2%
Output Voltage Regulation (Economy Line Mode) +/- 10%
Output Voltage Regulation (Battery Mode) +/- 2%
Output Receptacles (8) C13; (2) C19
Included Output Power Cables Includes 2 C13 to C14 and 1 C19 to C20 power cables
Load Management Receptacles Two switchable 4 outlet load banks (3 C13 and 1 C19 per bank)
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 14.97A
Nominal Input Voltage(s) Supported 200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS Input Connection Type C20 inlet
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 5 min. (2700w)
Half Load Runtime (min.) 13.5 min. (1350w)
Expandable Battery Runtime Supports extended runtime with optional external battery packs
External Battery Pack Compatibility BP72V15-2U(limit 1); BP72V28RT-3U(multi-pack compatible); BP72V18-2US(multi-pack compatible)
DC System Voltage (VDC) 72
Battery Recharge Rate (Included Batteries) 3.0 hours from 10% to 90% (typical, full load discharge)
Internal UPS Replacement Battery Cartridge RBC72S
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description Online, double-conversion power conditioning
Overvoltage Correction 2% output voltage regulation during overvoltages to 288
Undervoltage Correction 2% output voltage regulation during undervoltages to 160V (100% load), 130V (70% load), 100V (30% load)
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Interactive front-panel LCD interface reports UPS operating mode, detailed UPS status and site-power information; LCD interface also enables a variety of advanced UPS setup and configuration options
Switches 5 front panel switches: On/Off, Up, Down and Escape
Alarm Cancel Operation Power-fail alarm can be silenced by following on-screen prompts
Audible Alarm Audible alarm indicates power failure, low battery, overload and fault
LED Indicators 4 front panel LEDs: AC input (green), AC output (green), Battery (yellow), Fault (red)
SURGE / NOISE SUPPRESSION
UPS Dataline Suppression Details Single line dialup / network dataline protection included
EMI / RFI AC Noise Suppression Yes
AC Suppression Joule Rating 570
AC Suppression Response Time Instantaneous
PHYSICAL
Included Mounting Accessory Description 4 post installation accessories included
Installation Form Factors Supported with Included Accessories 4 post 19 inch rackmount
Installation Form Factors Supported with Optional Accessories 2 post rackmount(2POSTRMKITWM)
Optional Mounting Accessory Notes Upright tower configurations not recommended
Primary Form Factor Rackmount
UPS Power Module Dimensions (hwd, cm) 8.8 x 43.8 x 61.6
Rack Height (U Spaces) 2
UPS Power Module Weight (kg) 31.2
UPS Shipping Dimensions (hwd / cm) 24 x 56.0 x 76.0
Shipping Weight (kg) 38.2
Cooling Method Fan
UPS Housing Material Metal
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
Relative Humidity 5 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 933
AC Economy Mode BTU / Hr. (Full Load) 484
Battery Mode BTU / Hr. (Full Load) 1399
AC Mode Efficiency Rating (100% Load) >90%
AC Economy Mode Efficiency Rating (100% Load) >95%
Audible Noise <50dB at front side 1M
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
PowerAlert Software Available for download at www.tripplite.com
Communications Cable USB and DB9 cabling included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time No transfer time (0 ms.) in online, double-conversion mode; 4 ms. transfer time during economy mode operation
Low Voltage Transfer to Battery Power (Setpoint) 160V (100% load), 140V (66% load), 120V (33% load)
High Voltage Transfer to Battery Power (Setpoint) 288V
SPECIAL FEATURES
Grounding Lug Back panel grounding lug included
Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
High Availability UPS Features Automatic inverter bypass; Hot swappable batteries
Green Energy-Saving Features High efficiency economy mode operation; Individually controllable load banks
CERTIFICATIONS
UPS Certifications CE; ENERGY STAR Qualified; Meets FCC Part 15 Category A (EMI); Tested to CSA (Canada); Tested to EAC (Belarus, Kazakhstan, Russia); Tested to SASO (Saudi Arabia); Tested to UL1778 (USA)
UPS Certification Details Meets EMI approvals IEC62040-2:2006; FCC Part 15
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty
Connected Equipment Insurance (U.S., Canada & Puerto Rico) $250,000 Ultimate Lifetime Insurance